Specifications
IN P U T
Power Levels 300, 420, and 650 VA; see Model Selection Guide
Topology Standby
Operating Voltage 120 Vac models: 103 to 142 (default);
Range 88 to 142 Vac (user-selectable)
230 Vac models: 196 to 260 (default);
166 to 260 Vac (user-selectable)
Frequency 50/60 Hz
Frequency Range 57 to 63 Hz @ 60 Hz
47 to 53 Hz @ 50 Hz
Current 3.5A @ 120 Vac; 1.8A @ 230 Vac
Connections See Model Selection Guide
Protection Resettable circuit breaker
Total Harmonic Same as input
Distortion (THD)
TVSS Rating Total energy rating more than 240J, 6500A
Surge voltage let-through (percentage of applied ANSI
C62.41 Cat. A +6kV test waveform) 5%
AC OU T P U T, NO R M A L MO D E
Voltage 120 and 230 Vac; see Model Selection Guide
Frequency 50/60 Hz auto-selectable; same as input
Frequency Same as load
Regulation
Overload 110% + 10% overload for 3 minutes. SMPS load, pure sine
wave input. 120% + 10% for 10 cycles
Efficiency 96% straight through mode @ full load and fully charged
battery
AC OU T P U T, BAT T E RY MO D E
Voltage Regulation Nominal voltage ±5%; -10% at low battery
Waveform Step wave (synthesized sine)
Frequency 50/60 Hz ±1 Hz of auto-selected nominal frequency
Regulation
Transfer Time 4 milliseconds, typical
Efficiency >70%, 100% SMPS load
BAT T E RY
Backup Time See Battery Run Times table
Battery Recharge 12 hours to 95% usable capacity @ nominal line after full
Time load discharge
Start-On-Battery Startup with UPS batteries in absence of utility power
Battery 12 and 6 Vdc batteries; Valve-Regulated Lead Acid (VRLA),
minimum 3 year float service life at 25°C
Battery Protection Internal batteries protected by either a fuse or circuit
breaker. Fuse ratings: 30A/32 Vdc and 40A/32 Vdc
Charger Voltage 13.5 to 13.8 Vdc
Maximum Charge 12V battery = 0.7 ± 0.1A
Current 6V battery = 1.2 ± 0.1A
Replacement/ User-replaceable
Service
RE G U L AT O R Y STA N D A R D S A N D RE Q U I R E M E N T S
Safety 120 Vac models: UL1778, CAN/CSA C22.2 No. 107.1
230 Vac models: EN50091-1, C-Tick
EMI/EMC 120 Vac models: FCC Part 15 Class B
230 Vac models: EN50091-2
Immunity IEC 61000-4-2, -3, -4
Audible Noise < 40 dBA
Operating Altitude 3000m (10,000 ft max.)
Operating 0°C to 40°C, 0 to 1500 meters above sea level
Temperature 0°C to 35°C, 1500 to 3000 meters above sea level
Transit and -15°C to +55°C
Storage Temperature
Relative Humidity 0 to 95% noncondensing
ME C H A N I C A L
Dimensions See Model Selection Guide
and Weight
In a perfect world, your electrical
equipment would always receive clean
power. However, without UPS protection,
power quality can be erratic, causing serious
damage to your files and hardware.
Series 3 Power Protection
The Powerware 3115 is a Series 3 UPS,
meaning it protects your equipment from
three basic power problems: power failures,
power surges, and power sags.
These three power problems can cause
hardware damage, keyboard lockups,
data corruption, and data loss.
Acting as a defensive barrier between your
equipment and dirty power, the Powerware
3115 eliminates the threats caused by
power failures, power surges, and power
sags, thus increasing productivity and your
bottom line.
Power Failures
A complete loss of utility power that can be
caused by events such as lightning strikes,
grid over-demands, accidents, and natural
disasters.
Power Surges
With voltages above 110% of nominal,
surges can be triggered by rapid reduction
in power loads, heavy equipment being
turned off, or by utility switching.
Power Sags
The opposite of surges, sags are caused by a
startup of large loads, utility switching,
utility equipment failure, lightning, and
power service that is too small for the
demand.