Installation and OperationManualUninterruptible PowerSupply10 kVA -- 20 kVA25 kVA -- 40 kVA164201300 Rev. G9330

Pagina 2

xPowerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502F i g u r e 1 2 --- 8. E v e n t s --- A c t i v e 12 --- 6...

Pagina 3 - Table of Contents

8-- 2Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615028.2 Using the LCD Screen and PushbuttonsThe LCD screen on the Co

Pagina 4 - Section II Operation

8-- 3Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615028.3 Using the Main MenuThe UPS main menu allows you to display d

Pagina 5

8-- 4Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615028.3.2 System Event ScreensSelect EVENTS from the Main menu to di

Pagina 6

8-- 5Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615028.3.3 System Meter ScreensSelect METERS from the Main menu to di

Pagina 7

8-- 6Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502The Bypass screen shows the phase-to-neutral voltage, and freque

Pagina 8 - List of Figures

8-- 7Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502The Output Current Screen displays a real-time bar graph of the

Pagina 9

8-- 8Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615028.3.4 Setup Menu ScreensSelect SETUP from the Main menu to displ

Pagina 10 - 164201300 REV. G 061502

8-- 9Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502Select DATE &TIME from the System Setup menu to display the

Pagina 11 - List of Tables

8-- 10Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502Select SERIAL PORTS from the System Setup menu to display the S

Pagina 12

8-- 11Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502Select VERSIONS from the System Setup menu to display the Versi

Pagina 13 - Introduction

xiPowerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502List of TablesTa b l e 4 --- 1 . R e m o t e E P O W i r e Te r m i

Pagina 14 - System C onfigurations

8-- 12Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615028.4 System Controls ScreenSelect CONTROLS from the Main menu sc

Pagina 15 - Using This Manual

8-- 13Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502SYSTEM CONTROLSCHARGERBYPASS PPU ONNORMALMAINTENANCE BYPASSBYPA

Pagina 16

8-- 14Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615028.4.1 Charger Controls ScreenSelect CHARGER from the System Con

Pagina 17 - Safety Considerations

8-- 15Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615028.5 Unit Shutdown ScreenThe Unit Shutdown screen appears when t

Pagina 18 - Getting Help

8-- 16Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615028.6 Reading the Status IndicatorsThefivesymbolsontheleftsideoft

Pagina 19 - Installation

9-- 1Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502UPS Operating Instructions9.1 OperationThe following procedures

Pagina 20

9-- 2Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 06150212. O bserve the following messages appear sequentially on the P

Pagina 21 - Getting Started

9-- 3Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615029.4 Starting the Power Processing UnitTo start the Power Process

Pagina 22

9-- 4Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615029.5 Cold Starting the UPSTo start the UPS system when commercial

Pagina 23

9-- 5Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 06150213. O bserve the following messages appear sequentially on the P

Pagina 24

xiiPowerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502This Page Intentionally Left Blank.

Pagina 25

9-- 6Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615029.7 Transfer from Bypass to Normal ModeTo transfer the critical

Pagina 26

9-- 7Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615029.10 Transfer from Normal to Bypass Mode with UPSShutdown1. Tran

Pagina 27 - Installing the UPS System

9-- 8Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615029.13 Options Cabinet Maintenance Bypass TransferTo transfer the

Pagina 28 - 2.2 UPS Cabinet Installation

9-- 9Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615029.16 Using the REMOTE EMERGENCY POWER OFFSwitchAn UPS Emergency

Pagina 29

9-- 10Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502This Page Intentionally Left Blank.

Pagina 30 - REAR VIEW

10--1Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502Using Features10.1 GeneralThe many standard features of your UPS

Pagina 31 - Cabinet from the Pallet

10--2Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 06150210.4 Optional Remote Monitor PanelAs an option, you can install

Pagina 32

10--3Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502The RMP contains a local horn and the following backlit status i

Pagina 33

10--4Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502This Page Intentionally Left Blank.

Pagina 34

11- -1Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502Responding to System Events11.1 GeneralWhen the UPS system is r

Pagina 35 - CAUTION:

xiiiPowerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502IntroductionPowerware 9330 UPS true double conversion online powe

Pagina 36

11- -2Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 06150211.4 System Event MessagesWhen a system event occurs, a message

Pagina 37

11- -3Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502ALARMSMessage IndicationLogRelayPhoneHornCheck Inverter 1 4 1 H

Pagina 38

11- -4Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502ALARMSMessage IndicationLogRelayPhoneHornInput Phase R o tation

Pagina 39

11- -5Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502ALARMSMessage IndicationLogRelayPhoneHornRectifier Under Voltag

Pagina 40 - (Non–Permanent Mounting)

11- -6Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502NOTICESMessage Horn Phone Relay Log IndicationABS: Battery DCUV

Pagina 41 - (Permanent Mounting)

11- -7Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502NOTICESMessage IndicationLogRelayPhoneHornCalling Phone #2 2 No

Pagina 42

11- -8Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502NOTICESMessage IndicationLogRelayPhoneHornSBM IO 2 Not Reportin

Pagina 43

11- -9Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502STATUSMessage Horn Phone Relay Log IndicationAlarm Lamp No No 1

Pagina 44

11- -10Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502COMMANDSMessage Horn Phone Relay Log IndicationBypass Mode No

Pagina 45

12--1Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502Communications12.1 DescriptionThis chapter describes the serial

Pagina 46

xivPowerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502UPSCABINETBATTERYCABINETOPTIONSCABINETTypical Powerware 9330 (25 k

Pagina 47

12--2Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502321547698TXDRXDDSRRETURNDTRCTSRTSNOT USEDSERIAL PORT (DB--9)NOT

Pagina 48

12--3Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 06150212.5 Terminal ModeIn Terminal Mode, the user can request the fol

Pagina 49

12--4Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502F i g u r e 1 2 --- 3 . M a i n S c r e e n --- U P S O n B a t

Pagina 50

12--5Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502Figure 12---5. System ControlsFigure 12 ---6. Load Off

Pagina 51

12--6Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502F i g u r e 1 2 --- 7 . E v e n t s --- H i s t o r yF i g u r e

Pagina 52

12--7Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502Figure 12 ---9. Input MeterFigure 12---10. Output Meter

Pagina 53

12--8Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502Figure 12---11. Bypass MeterFigure 12---12. Output Current (Load

Pagina 54 - 2.5 Initial Startup

12--9Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502Figure 12---13. SetupFigure 12---14. Contrast Adjust

Pagina 55 - 2.6.1 Installation Checklist

12--10Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502Figure 12---15. Date and Time SetupFigure 12---16. Serial Port

Pagina 56

12--11Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502Figure 12 ---17. Versions

Pagina 57

xvPowerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502· Parallel System with one to four UPS modules with remote battery

Pagina 58 - 3.3 Battery Installation

12--12Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 06150212.5.2 Event History LogThis key sequence prints the entire Eve

Pagina 59

12--13Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502Inverter Version 0.97Machine Control Version 0.99Comm Server Ve

Pagina 60

12--14Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502This Page Intentionally Left Blank.

Pagina 61 - 3.4 Connecting Batteries

13--1Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502Remote Notification13.1 DescriptionRemote Notification provides

Pagina 62 - THIS SECTION

13--2Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 06150213.2 Remote Notification FeaturesRemote Notification provides th

Pagina 63

13--3Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 06150213.3 Description of OperationThe Remote Notification option perf

Pagina 64

13--4Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502· The UPS logs a successful notify to the event log when the rem

Pagina 65 - Power Off (EPO) Control

13--5Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 06150213.4 Hardware RequirementsThe following hardware components are

Pagina 66 - BOTTOM ENCL OSURE

13--6Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 06150213.5 Configuring the ModemThe modem must be programmed with the

Pagina 67

13--7Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615027. To program a group four number, key in [A], [T], [&], [Z]

Pagina 68

xviPowerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502· Chapter 8 -- Using the Control Panel -- describes the controls a

Pagina 69 - Monitor Panel

13--8Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615027. To program a group four number, key in [A], [T], [&], [Z]

Pagina 70

13--9Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 06150213.6.1 Default EventsThe default messages sent are listed in the

Pagina 71

13--10Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502This Page Intentionally Left Blank.

Pagina 72

14--1Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502Maintaining the UPS System14.1 GeneralThe components inside the

Pagina 73 - Operation

14--2Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502Observe these precautions when working on or around batteries:·

Pagina 74

14--3Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 06150214.3 Performing Preventive MaintenanceThe UPS system requires ve

Pagina 75 - Understanding UPS

14--4Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 06150214.4 Maintenance TrainingA basic training course, available from

Pagina 76

15--1Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502Product Specificat i ons15.1 Model NumbersThe UPS systems are ho

Pagina 77 - 6.2 UPS Modes

15--2Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 06150215.3 UPS System OutputDC Filtering Ripple voltage less than 0.5%

Pagina 78 - NORMAL MODE

15--3Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 06150215.4 Environmental SpecificationsOperating Temperature 0to40˚C w

Pagina 79

xviiPowerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502Safety ConsiderationsThe UPS cabinet is designed for industrial o

Pagina 80 - BYPASS MODE

15--4Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502This Page Intentionally Left Blank.

Pagina 81

A---1Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502Appendix A --- Customer InformationThe information in this appen

Pagina 82 - HIGH EFFICIENCY MODE

DESCRIPTION:DATE:DRAWING NO:1of17SHEET:REVISION:FNOTE:Callout letterandmap to drawing #164201300---6,,,111501ABCD164201300---1POWER WIRING INSTALLATIO

Pagina 83 - BATTERY MODE

DESCRIPTION:DATE:DRAWING NO:2of17SHEET:REVISION:ENOTE:Callout letterandmap to drawing #164201300---6,,,071501ABCD164201300---1POWER WIRING INSTALLATIO

Pagina 84

DESCRIPTION:DATE:DRAWING NO:3of17SHEET:REVISION:DNOTE:Callout letterandmap to drawing #164201300---6,,,053001ABPOWER WIRING INSTALLATION NOTES16420130

Pagina 85 - TEST MODE

DESCRIPTION:DATE:DRAWING NO:4of17SHEET:REVISION:ENOTE:Callout letterandmap to drawing #164201300---6,,,071501164201300---1POWER WIRING INSTALLATION NO

Pagina 86 - 6.3 Functional Description

DESCRIPTION:DATE:DRAWING NO:5of17SHEET:REVISION:DNOTE:Callout letterandmap to drawing #164201300---6,,,053001ABCD164201300---1POWER WIRING INSTALLATIO

Pagina 87

DESCRIPTION:DATE:DRAWING NO:6of17SHEET:REVISION:GNOTE:Callout letterandmap to drawing #164201300---6,,,061502ABCD164201300---1POWER WIRING INSTALLATIO

Pagina 88

DESCRIPTION:DATE:DRAWING NO:7of17SHEET:REVISION:DNOTE:Callout letterandmap to drawing #164201300---6,,,053001ABPOWER WIRING INSTALLATION NOTES16420130

Pagina 89 - Operational Controls

DESCRIPTION:DATE:DRAWING NO:8of17SHEET:REVISION:DNOTE:Callout letterandmap to drawing #164201300---6,,,053001164201300---1POWER WIRING INSTALLATION NO

Pagina 90

xviiiPowerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502For More InformationThis manual describes how to install and ope

Pagina 91

DESCRIPTION:DATE:DRAWING NO:9of17SHEET:REVISION:F111501NOTE: Customer ground, size 1/0, can berun in any conduit listed in Table R.POWER WIRING INSTAL

Pagina 92 - 7.3 UPS Standard Features

DESCRIPTION:DATE:DRAWING NO:10 of 17SHEET:REVISION:F111501NOTE: Customer ground, size 1/0, can berun in any conduit listed in Table R.POWER WIRING INS

Pagina 93 - 7.4 Options and Accessories

DESCRIPTION:DATE:DRAWING NO:11 of 17SHEET:REVISION:D053001NOTE: Customer ground, size 1/0, can berun in any conduit listed in Table R.POWER WIRING INS

Pagina 94 - 7.4.5 Parallel Cabinet

DESCRIPTION:DATE:DRAWING NO:12 of 17SHEET:REVISION:F111501POWER WIRING INSTALLATION NOTES164201300---1A --- 1 3Powerware 9330 (10 kVA--40 kVA) Install

Pagina 95 - 7.4.6 Communications

DESCRIPTION:DATE:DRAWING NO:13 of 17SHEET:REVISION:F111501POWER WIRING INSTALLATION NOTES164201300---1A --- 1 4Powerware 9330 (10 kVA--40 kVA) Install

Pagina 96 - 7.5 Safety Considerations

DESCRIPTION:DATE:DRAWING NO:14 of 17SHEET:REVISION:F111501POWER WIRING INSTALLATION NOTES164201300---1A --- 1 5Powerware 9330 (10 kVA--40 kVA) Install

Pagina 97

DESCRIPTION:DATE:DRAWING NO:15 of 17SHEET:REVISION:F111501POWER WIRING INSTALLATION NOTES164201300---1A --- 1 6Powerware 9330 (10 kVA--40 kVA) Install

Pagina 98

DESCRIPTION:DATE:DRAWING NO:16 of 17SHEET:REVISION:F111501164201300---1POWER WIRING INSTALLATION NOTESA --- 1 7Powerware 9330 (10 kVA--40 kVA) Install

Pagina 99 - Using the Control Panel

DESCRIPTION:DATE:DRAWING NO:17 of 17SHEET:REVISION:D053001164201300---1POWER WIRING INSTALLATION NOTESA --- 1 8Powerware 9330 (10 kVA--40 kVA) Install

Pagina 100

DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:G1of5051502CUSTOMER INTERFACE WIRINGINSTALLATION NOTES164201300---2A --- 1 9Powerware 9330 (10 kVA--40 kVA

Pagina 101 - 8.3 Using the Main Menu

Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502Section IInstallation

Pagina 102 - 8.3.2 System Event Screens

DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:G2of5061502CUSTOMER INTERFACE WIRINGINSTALLATION NOTESCSB CUSTOMER INTERFACERELAY #2 NCRELAY #2 RETURNRELA

Pagina 103 - 8.3.3 System Meter Screens

DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:G3of5061502CUSTOMER INTERFACE WIRINGINSTALLATION NOTESCSB CUSTOMER INTERFACEX---SLOT 2 RIBBON CONNECTORX--

Pagina 104

DESCRIPTION:DATE:DRAWING NO:4of5SHEET:REVISION:G051502CUSTOMER INTERFACE WIRINGINSTALLATION NOTES164201300---2A --- 2 2Powerware 9330 (10 kVA--40 kVA)

Pagina 105

DESCRIPTION:DATE:DRAWING NO:5of5SHEET:REVISION:G051502CUSTOMER INTERFACE WIRINGINSTALLATION NOTES164201300---2A --- 2 3Powerware 9330 (10 kVA--40 kVA)

Pagina 106 - 8.3.4 Setup Menu Screens

DESCRIPTION:DATE:DRAWING NO:1of2SHEET:REVISION:G061502PHYSICAL FEATURES AND REQUIREMENTS164201300---3A --- 2 4Powerware 9330 (10 kVA--40 kVA) Installa

Pagina 107 - 16 MAY 2000 09 42 YES

DESCRIPTION:DATE:DRAWING NO:2of2SHEET:REVISION:G061502PHYSICAL FEATURES AND REQUIREMENTS164201300---3A --- 2 5Powerware 9330 (10 kVA--40 kVA) Installa

Pagina 108 - SERIAL PORTS

A --- 2 6Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502DESCRIPTION:DATE:DRAWING NO:TYPICAL UPS SYSTEMSHEET:REVISION

Pagina 109

A --- 2 7Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502DESCRIPTION:DATE:DRAWING NO:TYPICAL UPS SYSTEMSHEET:REVISION

Pagina 110 - 8.4 System Controls Screen

DESCRIPTION:DATE:DRAWING NO:1of2UPS SYSTEM CONFIGURATIONSSHEET:REVISION:F164201300---5111501NOTE 2: Output Voltage must match BypassInput Voltage.NOTE

Pagina 111

DESCRIPTION:DATE:DRAWING NO:2of2UPS SYSTEM CONFIGURATIONSSHEET:REVISION:F164201300---5111501NOTE 2: Output Voltage must match BypassInput Voltage.NOTE

Pagina 112 - 8.4.1 Charger Controls Screen

iiPowerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502-------------------------------------------------------------------

Pagina 113 - 8.5 Unit Shutdown Screen

Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502This Page Intentionally Left Blank.

Pagina 114

A --- 3 0Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:GONELINE DRAWING

Pagina 115 - UPS Operating Instructions

A --- 3 1Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:FOPTIONS CABINET

Pagina 116

A --- 3 2Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:F2of10111501UPS

Pagina 117

A --- 3 3Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:F3of10111501UPS

Pagina 118 - 9.5 Cold Starting the UPS

A --- 3 4Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:F4of10111501INBY

Pagina 119

A --- 3 5Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:F5of10111501UPS

Pagina 120

A --- 3 6Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:F6of10111501UPS

Pagina 121 - Shutdown

A --- 3 7Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:F7of10111501UPS

Pagina 122

A --- 3 8Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:F8of10111501UPS

Pagina 123 - 9.16.1 To Use the REPO Switch

A --- 3 9Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:F9of10111501INBY

Pagina 124

Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615021-- 1nGetting Started1.1 Installing the UPSThe cabinet sections of th

Pagina 125 - Using Features

A --- 4 0Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:F10 of 10111501U

Pagina 126 - HORN SILENCE

A --- 4 1Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:F1of511150116420

Pagina 127

A --- 4 2Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:F2of5111501UPS C

Pagina 128

A --- 4 3Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:F3of5111501UPS C

Pagina 129 - Responding to System Events

A --- 4 4Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:F4of5111501LOCAT

Pagina 130 - 11.4 System Event Messages

A --- 4 5Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:F5of5111501LOCAT

Pagina 131

A --- 4 6Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:D1of605300116420

Pagina 132

A --- 4 7Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:D2of6053001UPS C

Pagina 133

A --- 4 8Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:D3of6053001UPS C

Pagina 134

A --- 4 9Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:D4of6053001LOCAT

Pagina 135

1-- 2Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502The basic environmental requirements for operation of the UPS sy

Pagina 136

A --- 5 0Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:D5of6053001LOCAT

Pagina 137

A --- 5 1Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:D6of6053001LOCAT

Pagina 138

A --- 5 2Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:DLOCATION OF OPT

Pagina 139 - Communications

A --- 5 3Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:GLOCATION OF OPT

Pagina 140 - SERIAL PORT (DB--9)

A --- 5 4Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:DLOCATION OF OPT

Pagina 141 - 12.5 Terminal Mode

A --- 5 5Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:D4of4053001CONDU

Pagina 142

A --- 5 6Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:DLOCATION OF OPT

Pagina 143 - Figure 12 ---6. Load Off

A --- 5 7Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:GLOCATION OF OPT

Pagina 144

A --- 5 8Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:DLOCATION OF OPT

Pagina 145 - Figure 12---10. Output Meter

A --- 5 9Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:D4of4053001LOCAT

Pagina 146 - Figure 12---11. Bypass Meter

Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615021-- 31.1.5 Inspecting and Unpacking Each CabinetThe first task in pre

Pagina 147 - Figure 12---13. Setup

A --- 6 0Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:FLOCATION OF BA

Pagina 148

A --- 6 1Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502Dimensions are in millimeters and [inches]DESCRIPTION:DATE:D

Pagina 149 - Figure 12 ---17. Versions

A --- 6 2Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:F2of2111501UPS C

Pagina 150 - 12.5.2 Event History Log

A --- 6 3Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502Dimensions are in millimeters and [inches]DESCRIPTION:DATE:D

Pagina 151 - Display Version 0.96

A --- 6 4Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502Dimensions are in millimeters and [inches]DESCRIPTION:DATE:D

Pagina 152

A --- 6 5Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:D3of4053001UPS C

Pagina 153 - Remote Notification

A --- 6 6Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:E4of4071501UPS C

Pagina 154

A --- 6 7Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:D1of2053001OPTIO

Pagina 155 - 13.3 Description of Operation

A --- 6 8Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:D2of2053001OPTIO

Pagina 156 - 13.3.3 Housekeeping

A --- 6 9Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:D1of2053001OPTIO

Pagina 157 - 13.4 Hardware Requirements

1-- 4Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502Figure 1 ---2. Powerware 9330 (25 kVA ---40 kVA) UPS Cabinet as

Pagina 158 - 13.5 Configuring the Modem

A --- 7 0Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:D2of2053001OPTIO

Pagina 159

A --- 7 1Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:D1of1053001BATTE

Pagina 160 - 13.6 UPS Se tup Configuration

A --- 7 2Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:G164201300---181

Pagina 161 - 13.6.1 Default Events

A --- 7 3Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:G2of2051502REMOT

Pagina 162

A --- 7 4Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:G164201300---191

Pagina 163 - Maintaining the UPS System

W--1Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502LIMITED FACTORY WARRANTY FOR THREE -PHASE POWERWARE PRODUCTSThis

Pagina 164

W--2Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502This Page Intentionally Left Blank.

Pagina 165

Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615021-- 53. Set each pallet on a firm, level surface, allowing a minimum

Pagina 166 - 14.4 Maintenance Training

1-- 6Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502This Page Intentionally Left Blank.

Pagina 167 - Product Specificat i ons

2-- 1Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502Installing the UPS System2.1 Preliminary Installation Informatio

Pagina 168 - 15.3 UPS System Output

2-- 2Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615022.2 UPS Cabinet InstallationTo install an UPS cabinet, perform t

Pagina 169

2-- 3Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502VENTEDFRONTPANELSOLIDFRONTPANELFRONTSHIPPINGBRACKET (3)PALLETSHI

Pagina 170

iiiPowerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502Table of ContentsIntroduction xiii...

Pagina 171

2-- 4Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502REARSHIPPINGBRACKET (3)PALLETSKID BOLTS (4)(3 PLACES)REMOVABLESK

Pagina 172 - Po werw are 9330---20/10

2-- 5Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615028. Remove three bolts, (2) in Figure 2---1, securing front shipp

Pagina 173

2-- 6Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502FRONT VIEWSOLIDFRONTPANELFRONTSHIPPINGBRACKET (3)PALLETSHIPPINGB

Pagina 174

2-- 7Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502REAR VIEWREARSHIPPINGBRACKET (3)PALLETSKID BOLTS (4)(4 PLACES)RE

Pagina 175

2-- 8Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615024. Remove four bolts, (1) in Figure 2---4, securing the rear shi

Pagina 176

2-- 9Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615022.2.3 Installing Optional Remote Battery Power Wiring to thePowe

Pagina 177

2-- 10Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615022.2.4 Installing Optional Remote Battery Power Wiring to thePow

Pagina 178

2-- 11Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615022.2.5 Installing UPS External Power Wiring1. Remove left front

Pagina 179

2-- 12Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615022.2.6 Installing Customer ConnectionsNOTE: If installing connec

Pagina 180

2-- 13Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615022.3 Battery Cabinet InstallationTo install optional battery cab

Pagina 181

ivPowerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615022.5 Initial Startup 2---28...

Pagina 182

2-- 14Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502BATTERYCONNECTORFigure 2---5. Battery Cabinet Installation ---

Pagina 183

2-- 15Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502BATTERYCONNECTORFigure 2---6. Battery Cabinet Installation ---

Pagina 184

2-- 16Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502BATTERYCONNECTORFigure 2---7. Battery Cabinet Installation ---

Pagina 185

2-- 17Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502BATTERYCONNECTORFigure 2---8. Battery Cabinet Installation ---

Pagina 186

2-- 18Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 06150214. Install s ide panel removed from the UPS cabinet to the rig

Pagina 187

2-- 19Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615028. If permanently mounting the system, proceed to step 15; othe

Pagina 188

2-- 20Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615022.4 Options Cabinet Installation2.4.1 Unloading the Options Cab

Pagina 189 - 5 amp minimum

2-- 21Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502Figure 2---9. Options Cabinet Installation --- Powerware 9330 (

Pagina 190 - CSB CUSTOMER INTERFACE

2-- 22Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502Figure 2---10. Options Cabinet Installation --- Powerware 9330

Pagina 191

2-- 23Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502Figure 2---11. Options Cabinet Installation --- Powerware 9330

Pagina 192 - CONTACT RATING:

vPowerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615027 Operational Controls and Features 7---1...7.1

Pagina 193 - Table Z Remote EPO

2-- 24Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502Figure 2---12. Options Cabinet Installation --- Powerware 9330

Pagina 194

2-- 25Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 06150213. Remove the top side panel mounting screw (tie/grounding bra

Pagina 195 - During Full Load Operation

2-- 26Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615022.4.3 Installing Options Cabinet Internal Power Wiring1. Remove

Pagina 196 - 164201300---4 1 of 2

2-- 27Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615022.4.4 Installing Options Cabinet External Power WiringNOTE: Rem

Pagina 197 - 164201300---4

2-- 28Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502NOTE: Remove Options cabinet PDM conduit landing plate to punch

Pagina 198

2-- 29Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615022.6.1 Installation Checklist-All packing materials and restrain

Pagina 199

2-- 30Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502Notes__________________________________________________________

Pagina 200

3-- 1Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502Installing and Connecting Batteries3.1 Important Safety Instruct

Pagina 201 - 164201300---7

3-- 2Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615023.2 Battery TypeThe following battery types are supplied in the

Pagina 202 - A --- 3 2

3-- 3Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502Figure 3---1. Battery Schematic --- Powerware 9330 (10 kVA ---20

Pagina 203 - A --- 3 3

viPowerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615029 UPS Operating Instructions 9---1...9

Pagina 204 - A --- 3 4

3-- 4Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502Figure 3---2. Battery Schematic --- Powerware 9330 (25 kVA ---40

Pagina 205 - A --- 3 5

3-- 5Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615023.3.2 Installing Internal Batteries in the Battery CabinetIf the

Pagina 206 - A --- 3 6

3-- 6Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615023. Remove screws securing internal safety shield panels and remo

Pagina 207 - A --- 3 7

3-- 7Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502BATTERYCONNECTRED TOBLACKREDBLACKCONNECTRED TOBLACKCONNECTORCONN

Pagina 208 - A --- 3 8

3-- 8Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615023.5 Installing and Connecting Re mote BatterySystemInstall and c

Pagina 209 - A --- 3 9

4-- 1Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502Installing a Remote EmergencyPower Off (EPO) Control4.1 Installa

Pagina 210 - 10 of 10

4-- 2Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502TB2TB1COVERBOTTOM ENCL OSUREFigure 4---2. Remote EPO Control (in

Pagina 211 - FRONT VIEW

4-- 3Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502Table 4---1. Remote EPO Wire TerminationsFrom RemoteEPO Switch(s

Pagina 212 - FRONT VIEW DETAIL

4-- 4Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502This Page Intentionally Left Blank.

Pagina 213 - LEFT VIEW

5-- 1Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502Installing a RemoteMonitor Panel5.1 Installation ProceduresAs an

Pagina 214

viiPowerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 06150213 Remote Notification 13---1...1

Pagina 215 - TOP VIEW

5-- 2Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615025.2 To i n s t a l l a n R M P :NOTE: 1. Before installing an RM

Pagina 216

5-- 3Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502PLUG-IN TERMINALTO REMOTE MONITORCABLE EXITFOR1/2” CONDUITOPENIN

Pagina 217 - POWER TERMINALS

5-- 4Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502This Page Intentionally Left Blank.

Pagina 218

Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502Section IIOperation

Pagina 219

Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502This Page Intentionally Left Blank.

Pagina 220

6-- 1Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502Understanding UPSOperation6.1 Looking Inside the UPS SystemThe P

Pagina 221 - X4 X3 X2 X1

6-- 2Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502DIGITALAC INPUT TOAC INPUT TOAC OUTPUTINPUTRECTIFIERINVERTERFILT

Pagina 222

6-- 3Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615026.2 UPS ModesThe UPS system functions automatically to supply AC

Pagina 223 - (SEE SHEET 3 FOR DETAILS)

6-- 4Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615026.2.1 Normal ModeFigure 6---2 shows the path of electrical power

Pagina 224

6-- 5Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502The battery charger derives its input from the unregulated DC ou

Pagina 225

viiiPowerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502List of FiguresFigure 1---1. Powerware 9330 (10 kVA---20 kVA)Cabi

Pagina 226

6-- 6Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615026.2.2 Bypass ModeThe U PS automatically switches to Bypass mode

Pagina 227 - NEUTRAL TERMINALS

6-- 7Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502the inverter rectifier. The static switch being an electronicall

Pagina 228 - DESIGNATION

6-- 8Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615026.2.3 High Efficiency ModeWhen the UPS is operating in High Effi

Pagina 229

6-- 9Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615026.2.4 Battery ModeThe U PS transfers to Battery mode automatical

Pagina 230 - BATTERY CABINET TERMINALS

6-- 10Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502If the input power fails to return or is not within the accepta

Pagina 231

6-- 11Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615026.2.5 Test and Maintenance Bypass ModesAn internal maintenance

Pagina 232

6-- 12Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502CB1CB2K1K5K3K2OpenClosedBreakersContactorsMain Power FlowEnergi

Pagina 233

6-- 13Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615026.3.2 Boost Converter and Neutral RegulatorA Boost Converter co

Pagina 234

6-- 14Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502This Page Intentionally Left Blank.

Pagina 235

7-- 1Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502Operational Controlsand Features7.1 GeneralThe UPS system should

Pagina 236

ixPowerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502F i g u r e 6 --- 1 . M a i n E l e m e n t s o f t h e U P S S y s

Pagina 237 - OPTIONS CABINET

7-- 2Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502CONTROLPANELAC INP UTBREAKERBATTERYBREAKER CB2BYPASSBREAKERBATTE

Pagina 238

7-- 3Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502CONTROLPANELBATTERYBREAKERUPSCABINETAC INP UTBREAKER CB1COLDSTAR

Pagina 239

7-- 4Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615027.2.2 UPS Circuit BreakersThe UPS can contain as many as 10 circ

Pagina 240

7-- 5Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502Summary Alarm ContactsAlarm contacts are provided for connection

Pagina 241 - BATTERY CABINET

7-- 6Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615027.4.2 Remote Monitor PanelAn optional Remote Monitor Panel (RMP)

Pagina 242 - 164201300---18

7-- 7Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615027.4.6 CommunicationsModemAn optional modem is available for use

Pagina 243

7-- 8Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615027.5 Safety ConsiderationsThe UPS enclosure is designed for indus

Pagina 244

7-- 9Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 0615027.6 Symbols, Controls, and IndicatorsThese symbols may appear on

Pagina 245

7-- 10Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502This Page Intentionally Left Blank.

Pagina 246

8-- 1Powerware 9330 (10 kVA--40 kVA) Installation and Operation164201300 REV. G 061502Using the Control Panel8.1 DescriptionThis chapter describes the