UPS SIDECAR ONELINE DRAWINGS
062806B
MAINTENANCE BYPASS WITH BIB CONFIGURATION
40/20, 40/30, 40/40, 80/40, 80/50, 80/60, AND 80/80 kVA,
208/208V AND 480/480V
WITH UPS SERIAL NUMBER SEVENTH DIGIT AT “A” OR “B”
DESCRIPTION:
DATE:
DRAWING NO: SHEET:
REVISION:
K1
K5
K3
Po werware 9390 UPS CABINET
UPS Sidecar
MAINTENANCE
BYPASS SWITCH
(MBP)
AC INPUT
TO BYPASS
A
MAINTENANCE
ISOLATION SWITCH
(MIS)
BYPASS INPUT
BREAKER (BIB)
SINGLE-FEED
JUMPER
(REMOVE FOR
DUAL-FEED)
C
AC OUTPUT
TO
CRITICAL LOAD
E4. E5
BAT TERY
CONVER TER
INVERTER
RECTIFIER
NOTE 1. Remove jumper for dual- feed.
2. If the load requires a neutral, a bypass
neutral feeder must be supplied.
SERIAL NUMBER SEVENTH
DIGITAT“A”or“B”
164201546---3 5 of 11
E6, E7, E8
E9, E10, E11
INSTALLATION INFORMATION
EATON Powerware
®
9390 UPS Sidecar Installation and Operation Manual S 164201586 Rev E www.powerware.com