POWER WIRING INSTALLATION NOTES
092107
DESCRIPTION:
DATE:
DRAWING NO: SHEET:
REVISION:
D
164201546---4 6 of 10
INSTALLATION INFORMATION
EATON Powerware
®
9390 UPS Sidecar Installation and Operation Manual S 164201586 Rev E www.powerware.com
A-22
Table I. UPS Sidecar Maintenance Bypass Power Cable Terminations
80/40, 80/50, 80/60, 80/80, 208/208V and 160/100, 160/120, 160/160, 480/480V
Terminal Function Function
Size of Pressure
Termination
Tightening Torque
Nm (lb in)
Type
Screw
AC Input to Maintenance
Bypass or Optional BIB
Phase A
1 --- 2/0---250 kcmil
1 --- 2/0---500 kcmil
31.1 (275)
31.1 (275)
5/16 Hex
3/8 Hex
Phase B
1 --- 2/0---250 kcmil
1 --- 2/0---500 kcmil
31.1 (275)
31.1 (275)
5/16 Hex
3/8 Hex
Phase C
1 --- 2/0---250 kcmil
1 --- 2/0---500 kcmil
31.1 (275)
31.1 (275)
5/16 Hex
3/8 Hex
AC Input to Optional RIB
Phase A
1 --- 2/0---250 kcmil
1 --- 2/0---500 kcmil
31.1 (275)
31.1 (275)
5/16 Hex
3/8 Hex
Phase B
1 --- 2/0---250 kcmil
1 --- 2/0---500 kcmil
31.1 (275)
31.1 (275)
5/16 Hex
3/8 Hex
Phase C
1 --- 2/0---250 kcmil
1 --- 2/0---500 kcmil
31.1 (275)
31.1 (275)
5/16 Hex
3/8 Hex
AC Output to Critical Load
Phase A
1 --- 2/0---250 kcmil
1 --- 2/0---500 kcmil
31.1 (275)
31.1 (275)
5/16 Hex
3/8 Hex
Phase B
1 --- 2/0---250 kcmil
1 --- 2/0---500 kcmil
31.1 (275)
31.1 (275)
5/16 Hex
3/8 Hex
Phase C
1 --- 2/0---250 kcmil
1 --- 2/0---500 kcmil
31.1 (275)
31.1 (275)
5/16 Hex
3/8 Hex
Table J. UPS Sidecar 1+1 Parallel Redunda nt Power Cable Terminations
40/20, 40/30, 40/40, 208/208V and 80/40, 80/50, 80/60, 80/80, 480/480V
Terminal Function Function
Size of Pressure
Termination
Tightening Torque
Nm (lb in)
Type
Screw
AC Input from UPM2 to
MOB 2 (standalone
installation)
Phase A 1 --- # 4 --- 3 5 0 k c m i l
20.3 (180)
3/16 Hex
Phase B 1 --- # 4 --- 3 5 0 k c m i l
20.3 (180)
3/16 Hex
Phase C 1 --- # 4 --- 3 5 0 k c m i l
20.3 (180)
3/16 Hex
AC Output to Critical Load
(without SLB) Terminal
Block
Phase A 1 --- # 1 4 --- 2 / 0
13.5 (120)
3/16 Hex
Phase B 1 --- # 1 4 --- 2 / 0
13.5 (120)
3/16 Hex
Phase C 1 --- # 1 4 --- 2 / 0
13.5 (120)
3/16 Hex
AC Output to Critical Load
(with SLB)
Phase A 1 --- # 4 --- 3 5 0 k c m i l
20.3 (180)
3/16 Hex
Phase B 1 --- # 4 --- 3 5 0 k c m i l
20.3 (180)
3/16 Hex
Phase C 1 --- # 4 --- 3 5 0 k c m i l
20.3 (180)
3/16 Hex
Neutral (80/480) Neutral 4 --- # 1 4 --- 1 / 0 5.6 (50) Slotted
Neutral (40/208) Neutral 8 --- # 6 --- 2 5 0 k c m i l 42.4 (375) 5/16 Hex
Ground Ground 2 --- # 1 4 --- 1 / 0 5.6 (50) Slotted